Specifications
Engine Cummins 6BTA5.9-G3 turbocharged, after-cooled, 207 bhp, 6 cylinder diesel. Meets EPA Mobile Off Highway, and California SCAQMD and CARB permitting requirements. Maximum output: 1100 Amps continuous, 1200 Amps standby @120 Volts.
Frequency Control Woodward digital electronic controller with integrated actuator. No external linkage to maintain. Crystal accuracy for HMI lighting.
Controller Engine control and monitoring, AC monitoring, fault and pre-fault systems are provided by a microprocessor-based system. All readouts are digital and are listed below. Weather-proof glass cover.
|
Monitoring |
Faults and Pre-Faults |
|
AC Voltage - All Legs |
Oil Pressure Fault/Pre-Fault |
|
Amperage - All Legs |
Water Temp Fault/Pre-Fault |
|
Frequency - All Legs |
Over Crank Fault |
|
Oil Pressure |
Over Speed Fault |
|
Water Temperature |
Low Fuel Fault and Pre-Fault |
|
Battery Voltage |
Low Battery Pre-Fault |
|
Fuel Level |
Defective Oil Sending Unit Pre-Fault |
|
Time To Next Service |
Defective Water Sending Unit Pre-Fault |
Generator Lima/Marathon MagnaPLUS 125KW (1,041 amps @ 120V) three phase. 75KW (625 amps @ 120V) single phase @ class F 130 deg rating. 135KW (1,125 @ 120V) three phase, 80KW (667 amps @ 120V) single phase @ class H 150 deg rating. Marine rated rectifier with surge suppression. CSA listed.
Voltage Regulator Lima/Marathon SE 350A with remote voltage adjustment. UL and CSA listed.
Circuit Breaker 400 amp breaker protects equipment in either single or three phase. Weather-proof glass cover. UL and CSA listed.
Electrical Connection USA - 18 hole Cam-Lok - E1016 panel includes 3 male grounds, 3 female grounds, 3 neutral, 3 leg one, 3 leg two and 3 leg three. Two Edison 20A outlets with 20A breakers and one 100A Union connector with 100A breaker provided for convenience outlets.
CANADA - Cam-Loc 1016 replaced with 400A Ball Nose Connectors. UL and CSA listed.
Dimensions Generator: L 84" W 36" H 62"
Generator with 150 gallon tank: L 84" W 73" H 74"
Generator, 150 gallon tank, trailer: L 154" W 90" H 87"
Noise Level Less than 50 dB(A) @ 50 feet.
|
Optional Accessories
Remote Annunciator Remote monitoring of engine and generator via cable. Operates up to 1700 yards. Includes 50' cable. Available with remote start.
Paralleling System with Vacuum Contactor "The most advanced, comprehensive paralleling solution available today." Four functions in one:
- Display and Programming Panel
- Isochronous Load Sharing
- Auto-Synchronizer
- Load Management
Electronic Service Kit Provides total redundancy of all electronic parts. Each component can be installed in less than ten minutes. Includes:
- Woodward Engine Speed Controller
- Magnetic Pick-up
- Engine/Generator Controller Board Set
- Voltage Regulator
- Voltage Adjust Pot
480 Volt 277/480 Volt 3 phase in addition to standard voltages.
Trailer 2 Dexter Torflex axles, 15" aluminum wheels with C rated tires, surge hydraulic brakes with LitePOWER Brake Retarder or Electric Brakes, 3 position coupler with your choice of 2" ball, 2-5/16" ball or drawbar (for Pintle Hook), DOT lighting and markings, 7000 lbs. (3174 kg) GVW standard.
Fuel Tank 150 gallons. Required for LitePOWER trailer but not for truck or stationary mounting. Includes integrated fork pockets and guide pin location for easy mounting to trailer.
Jockey Box Tanks Dual 60 gallon tanks for truck mounting.
| Running Time - with 150 gallon tank |
| Load |
% of Load |
Hours |
| 1200A |
100% |
14:20 |
| 1100A |
92% |
15:45 |
| 825A |
69% |
20:50 |
| 550A |
46% |
28:50 |
| 275A |
23% |
55:30 |
Weight - Generator
Including fluids: 4015 lbs. (1825 kg)
Weight - Complete Package
Generator, 150 Gallon Tank, Trailer and Fuel: 6400 lbs. (2909 kg)
|